Chapter 2 Built-in Cnet communication
2-33
B
u
ilt
-in
C
omm
2.4.4
Modbus Client Service
Modbus protocol is specified open protocol used between client-server, which executes reading/writing data according to
function code. Communication between devices that use Modbus protocol uses Client-server function in which only one
client processes the data.
1) Channel setting
Cnet I/F module is available to define driver type for P2P service about each channel. However, active mode in the
standard settings should be set as “Use P2P settings”.
2) P2P block setting
There are two commands; Write (writes memory of self station to destination station’s memory area) and Read (reads
memory of destination memory and saves it in the memory area of self station)
Setting methods of both RTU and ASCII clients are same.
①
②
③
④
⑤
⑥
⑦
⑧
⑨
No.
Type
Block type
Meaning
1
Channel
Driver name changes according to driver set in the P2P Driver.
2
P2P
function
1. Read : when reading the destination station’s memory
2. Write: when writing self-station’s memory to destination station’s
memory.
Summary of Contents for XBE-DC08A
Page 124: ...Main Chapter 1 Configuration and Operation Mode of Programs 1 27 1 Memory block diagram ...
Page 504: ...Position Chap 6 Commands 6 61 6 11 Function blocks related to Servo Drive ...
Page 644: ...Positioning Chapter 8 Functions 8 91 ...
Page 727: ...Positioning Chapter 9 Positioning Error Information Solutions 9 13 ...
Page 1207: ...Appendix 2 Dimension App2 2 2 Analog Type XEC DN32UA ...
Page 1209: ...Appendix 2 Dimension App2 4 XBE DC08A XBE DC16A XBE TN08A XBE TN16A XBE DR16A XBE RY08A ...
Page 1210: ...Appendix 2 Dimension App2 5 4 Extension Cnet I F Module XBL C41A XBL C21A ...