Sy
st
em
Chapter 6 Troubleshooting
6-13
Error
code
(Dec)
Error cause
Action
(restart mode after taking an action)
Operation
status
LED
status
Diagnosis
point
40
Scan time of program
during operation
exceeds the scan
watchdog time
designated by
parameter.
After checking the scan watchdog time designated
by parameter, modify the parameter or the
program and then restart.
Warning
0.5 second
Flicker
While
running the
program
41
Operation error
occurs while
running the user
program.
Remove
operation error → reload the program
and restart.
Warning
0.5 second
Flicker
While
running the
program
44
Timer index user
error
After reloading a timer index program modification,
start
Warning
0.5 second
Flicker
Scan end
50
Heavy error of
external device
Refer to Heavy error detection flag and modifies
the device and restart. (Acc. Parameter)
Heavy error
1 second
Flicker
Scan end
55
Task confliction
Check task occurrence
Heavy error
0.5second
Flicker
Every time
60
E_STOP function
executed
After removing error causes which starts E_STOP
function in program, power reinput
Heavy error
1 second
Flicker
While
running the
program
Error
code
Error cause
Action
(restart mode after taking an action)
Operation
status
LED
status
Diagnosis
point
500
Data memory backup not
possible
If not error in battery, power reinput
Remote mode is switched to STOP mode.
Warning
1 second
Flicker
Reset
501
Abnormal clock data
Setting the time by XG5000 if there is no error
Warning
0.1 second
Flicker
Ordinary
time
502
Battery voltage falling
Battery change at power On status
Warning
0.1 second
Flicker
Ordinary
time
Summary of Contents for XBE-DC08A
Page 124: ...Main Chapter 1 Configuration and Operation Mode of Programs 1 27 1 Memory block diagram ...
Page 504: ...Position Chap 6 Commands 6 61 6 11 Function blocks related to Servo Drive ...
Page 644: ...Positioning Chapter 8 Functions 8 91 ...
Page 727: ...Positioning Chapter 9 Positioning Error Information Solutions 9 13 ...
Page 1207: ...Appendix 2 Dimension App2 2 2 Analog Type XEC DN32UA ...
Page 1209: ...Appendix 2 Dimension App2 4 XBE DC08A XBE DC16A XBE TN08A XBE TN16A XBE DR16A XBE RY08A ...
Page 1210: ...Appendix 2 Dimension App2 5 4 Extension Cnet I F Module XBL C41A XBL C21A ...