Chapter 7 EMC Standard
7-1
Chapter 7 EMC Standard
The following explains contents, diagnosis and corrective actions for various errors that can occur during system operation.
7.1 Requirements for Conformance to EMC Directive
The EMC Directive specifies the products must “be so constructed that they do not cause excessive electromagnetic
interference (emissions) and are not unduly affected by electromagnetic interference (immunity)”. The applicable products
are requested to meet these requirements.
This section summarizes the precautions on conformance to the EMC Directive of the machinery assembled using PLC
XGB series. The details of these precautions are based on the requirements and the applicable standards control.
However, LSIS will not guarantee that the overall machinery manufactured according to the these details conforms to the
below-described directives. The method of conformance to the EMC directive and the judgment on whether or not the
machinery conforms to the EMC Directive must be determined finally by the manufacturer of the machinery.
7.1.1 EMC Standard
The standards applicable to the EMC Directive are listed below.
Table13-1
Specification
Test item
Test details
Standard value
EN50081-2
EN55011
Radiated noise
*
2
Electromagnetic emissions from the
product are measured
30~230
㎒
QP : 50
㏈㎶
/m
*
1
230~1000
㎒
QP : 57
㏈㎶
/m
EN55011
Conducted noise
Electromagnetic emissions from the
product to the power line is measured
150~500
㎑
QP : 79
㏈
Mean: 66
㏈
500~230
㎒
QP : 73
㏈
Mean: 60
㏈
EN61131-2
EN61000-4-2
Electrostatic
immunity
Immunity test in which static electricity is
applied to the case of the equipment
15
㎸
Aerial discharge
8
㎸
Contact discharge
EN61000-4-4
Fast transient
burst noise
Immunity test in which burst noise is
applied to the power line and signal lines
Power line: 2
㎸
Digital /O : 1
㎸
Analog I/O, signal lines: 1
㎸
EN61000-4-3
Radiated field AM
modulation
Immunity test in which field is irradiated to
the product
10Vm,26~1000
㎒
80%AM modulation@ 1
㎑
EN61000-4-12
Damped oscillatory
wave immunity
Immunity test in which a damped
oscillatory wave is superimposed on the
power line
Power line: 1
㎸
Digital I/O (24V or higher): 1
㎸
*
1) QP: Quasi-peak value, Mean: Average value
*
2) The PLC is an open type device (device installed to another device) and must be installed in a conductive control
panel. The tests for the corresponding items were performed while the PLC was installed inside a control panel.
Summary of Contents for XBE-DC08A
Page 124: ...Main Chapter 1 Configuration and Operation Mode of Programs 1 27 1 Memory block diagram ...
Page 504: ...Position Chap 6 Commands 6 61 6 11 Function blocks related to Servo Drive ...
Page 644: ...Positioning Chapter 8 Functions 8 91 ...
Page 727: ...Positioning Chapter 9 Positioning Error Information Solutions 9 13 ...
Page 1207: ...Appendix 2 Dimension App2 2 2 Analog Type XEC DN32UA ...
Page 1209: ...Appendix 2 Dimension App2 4 XBE DC08A XBE DC16A XBE TN08A XBE TN16A XBE DR16A XBE RY08A ...
Page 1210: ...Appendix 2 Dimension App2 5 4 Extension Cnet I F Module XBL C41A XBL C21A ...