Chapter 2 Built-in Cnet communication
2-10
B
u
ilt
-in
C
omm
2.2 Cnet Communication System Configuration
Communication system by using XGB built-in communication function is diverse. In this chapter, it describes system
configuration example.
1:1 Connection to PC (HMI) (No Modem)
2.2.2
PC (HMI) and XBCU main unit are connected by RS-232C or RS-485 channel, PC (HMI) and PLC is connected by
1:1 without modem. In most case, PC (HMI) acts as client and Cnet I/F module acts as server which respond request
of PC (HMI). Since there is no modem, in case of using RS-232C channel, communication distance is max 15m, in
case of using RS-422 channel, communication distance is max 500m. Operation mode of Cnet I/F is set according to
PC (HMI)’s communication method.
1) In case of using 1:1 connection with normal PC
•
Wiring method
External form of
PC
PC
Connection number and signal
direction
XGB main unit
XGB external
form
Pin no.
Pin no.
Signal
name
1
1
485-
2 (RXD)
2
485+
3(TXD)
3
SG
4
4
TX
5(GND)
5
RX
6
7
8
9
In case of using channel 2, connect 485+ and 485- of RS485 terminal.
XGB main unit
built-in communication
Female Type
Summary of Contents for XBE-DC08A
Page 124: ...Main Chapter 1 Configuration and Operation Mode of Programs 1 27 1 Memory block diagram ...
Page 504: ...Position Chap 6 Commands 6 61 6 11 Function blocks related to Servo Drive ...
Page 644: ...Positioning Chapter 8 Functions 8 91 ...
Page 727: ...Positioning Chapter 9 Positioning Error Information Solutions 9 13 ...
Page 1207: ...Appendix 2 Dimension App2 2 2 Analog Type XEC DN32UA ...
Page 1209: ...Appendix 2 Dimension App2 4 XBE DC08A XBE DC16A XBE TN08A XBE TN16A XBE DR16A XBE RY08A ...
Page 1210: ...Appendix 2 Dimension App2 5 4 Extension Cnet I F Module XBL C41A XBL C21A ...