B
asi
s
Chapter 4 Built-in High-speed Counter Function
4-8
(b) Ring count
Set Ring Counter Min. Value and Max. value. Preset value and compared set value should be in range of ring
counter min. value and max. value.
Ring counter max. and min value is saved at the following special K area.
type
Area per each channel (Double word)
Ref.
Ch.0
Ch.1
Ch.2
Ch.3
Ch.4
Ch.5
Ch.6
Ch.7
Ring counter
min. value
%KD154
%KD169
%KD184
%KD199
%KD1114 %KD1129
%KD1144 %KD1159
-
Ring counter
max. value
%KD155
%KD170
%KD185
%KD200
%KD1115 %KD1130
%KD1145 %KD1160
-
▪ Range of Ring counter: user defined min. value ~ user defined max. value
▪ Counter display: in case of using ring counter, user defined max. value is not displayed.
1) During increasing count
Even if count value exceeds user-defined maximum value during increasing count, Carry only occurs and
count does not stop differently to Linear Count.
Carry
Ring count max.
value
Input pulse
: not included
: included
Count start
Ring count min.
value
Carry/borrow reset
Summary of Contents for XBE-DC08A
Page 124: ...Main Chapter 1 Configuration and Operation Mode of Programs 1 27 1 Memory block diagram ...
Page 504: ...Position Chap 6 Commands 6 61 6 11 Function blocks related to Servo Drive ...
Page 644: ...Positioning Chapter 8 Functions 8 91 ...
Page 727: ...Positioning Chapter 9 Positioning Error Information Solutions 9 13 ...
Page 1207: ...Appendix 2 Dimension App2 2 2 Analog Type XEC DN32UA ...
Page 1209: ...Appendix 2 Dimension App2 4 XBE DC08A XBE DC16A XBE TN08A XBE TN16A XBE DR16A XBE RY08A ...
Page 1210: ...Appendix 2 Dimension App2 5 4 Extension Cnet I F Module XBL C41A XBL C21A ...