Po
sit
io
n
in
g
Chapter 8 Functions
8-82
(3) Restrictions
(a) Operation pattern of speed control has to be set as “End” or “Go on”. If “Continuous” is set as, error (error code:236)
arises and speed control may not be executed.
(b) If the value of goal position is 0, speed/position switching command may not be executed. In this case, it continues to
operate with speed control.
(4) Setting example of operation data
Items
Setting value
Description
Control method
Absolute, Single axis
speed control
When executing speed/position switching control, set single axis speed control
Operating method
Singular, End
When executing speed/position switching control, set “end” or “continuous”
Goal position
[pls]
10000
After inputting speed/position switching control, set moving amount to position.
Operating speed
[pls/s]
1000
Set the operating speed of speed/position switching control
Acc. no.
No1
Set acc. no. used in acceleration (no.1~4)
Dec. no.
No.2
Set dec. no. used in deceleration (no.1~4)
M code
0
Set it when user needs to execute another auxiliary work synchronizing with
speed/position switching control
Dwell time
500
Set dwell time(ms) between switching command’s inputting and positioning
completion’s outputting
Summary of Contents for XBE-DC08A
Page 124: ...Main Chapter 1 Configuration and Operation Mode of Programs 1 27 1 Memory block diagram ...
Page 504: ...Position Chap 6 Commands 6 61 6 11 Function blocks related to Servo Drive ...
Page 644: ...Positioning Chapter 8 Functions 8 91 ...
Page 727: ...Positioning Chapter 9 Positioning Error Information Solutions 9 13 ...
Page 1207: ...Appendix 2 Dimension App2 2 2 Analog Type XEC DN32UA ...
Page 1209: ...Appendix 2 Dimension App2 4 XBE DC08A XBE DC16A XBE TN08A XBE TN16A XBE DR16A XBE RY08A ...
Page 1210: ...Appendix 2 Dimension App2 5 4 Extension Cnet I F Module XBL C41A XBL C21A ...