Spe
ci
al
Chapter 1 Embedded Analog
1-17
1.5.5 Hold Last Value Function
When input signal exceeds the effective range, last input value is held. This function can be set for each channel by I/O
parameter setting or user program.
1) Used input range
In the channels that allow the hold last value function, the actual ranges provided within each digital conversion value
are shown. For example, in case of operating output data type of unsigned value, original digital output value is shown
from -192 to 16,191. However, if this function is allowed, it will be shown from 0 to 16,000. It is recommended that the
function should be setting when the input value is in the actual range.
(1) Digital output value depending on input range (unsigned value, signed value, percentile value)
Classification
Unsigned value
Signed value
Precise value
Percentile value
Function disabled
-192~16191
-8192~8191
(2) Reference
-120~10119
Function enabled
0~16000
-8000~8000
0~10000
(2) Digital output value depending on input range (Precise value)
Analog input range
Classification
Precise value
4 ~ 20
㎃
Function disabled
3808~20191
Function enabled
4000~20000
0 ~ 20
㎃
Function disabled
-240~20239
Function enabled
0~20000
1 ~ 5V
Function disabled
952~5047
Function enabled
1000~5000
0 ~ 5V
Function disabled
-60~5059
Function enabled
0~5000
0 ~ 10V
Function disabled
-120~10119
Function enabled
0~10000
-10 ~ 10V
Function disabled
-10240~10239
Function enabled
-10000~10000
2) Operation
When operating with 4 ~ 20mA while being enabled this function, output value for input value change of the moment
is as follows. (Output data type : In case of 0~16,000)
Input current(
㎃
)
12
㎃
3
㎃
4
㎃
12
㎃
21
㎃
20
㎃
Digital output value
8000
8000
0
8000
8000
16000
Remarks
-
Hold last
value
-
-
Hold last
value
-
Summary of Contents for XBE-DC08A
Page 124: ...Main Chapter 1 Configuration and Operation Mode of Programs 1 27 1 Memory block diagram ...
Page 504: ...Position Chap 6 Commands 6 61 6 11 Function blocks related to Servo Drive ...
Page 644: ...Positioning Chapter 8 Functions 8 91 ...
Page 727: ...Positioning Chapter 9 Positioning Error Information Solutions 9 13 ...
Page 1207: ...Appendix 2 Dimension App2 2 2 Analog Type XEC DN32UA ...
Page 1209: ...Appendix 2 Dimension App2 4 XBE DC08A XBE DC16A XBE TN08A XBE TN16A XBE DR16A XBE RY08A ...
Page 1210: ...Appendix 2 Dimension App2 5 4 Extension Cnet I F Module XBL C41A XBL C21A ...