Chapter 7 EMC Standard
7-3
(2) Connection of power and earth wires
Earthing and power supply wires for the PLC system must be connected as described below.
(a) Earth the control panel with a thick wire so that a low impedance connection to ground can be ensured even at high frequencies.
(b) The function of LG (Line Ground) and FG (Frame Ground) terminals is to pass the noise generated in the PLC system to the ground,
so an impedance that is as low as possible must be ensured.
(c) The earthing wire itself can generate the noise, so wire as short and thick to prevent from acting as an antenna.
(d) Attach ferrite core
under the power cable to satisfy CE specification.
[
ferrite core
]
manufacture
name
External Dimension (mm)
maximum
cable
diameter
(mm)
address
A
B
C
D
Laird
28A3851-0A2
30.00
13.00
33.70
30.00
12.85
www.lairdtech.com
Laird
28A5776-0A2
29.20
20.00
42.00
42.00
19.40
www.lairdtech.com
Coilmaster
C2L RU130B
31.50
13.00
33.00
31.50
13.00
www.coilmaster.com.tw
TDK
ZCAT3035-1330
30.00
13.00
34.00
30.00
13.00
www.tdk.com
ferrite core
Summary of Contents for XBE-DC08A
Page 124: ...Main Chapter 1 Configuration and Operation Mode of Programs 1 27 1 Memory block diagram ...
Page 504: ...Position Chap 6 Commands 6 61 6 11 Function blocks related to Servo Drive ...
Page 644: ...Positioning Chapter 8 Functions 8 91 ...
Page 727: ...Positioning Chapter 9 Positioning Error Information Solutions 9 13 ...
Page 1207: ...Appendix 2 Dimension App2 2 2 Analog Type XEC DN32UA ...
Page 1209: ...Appendix 2 Dimension App2 4 XBE DC08A XBE DC16A XBE TN08A XBE TN16A XBE DR16A XBE RY08A ...
Page 1210: ...Appendix 2 Dimension App2 5 4 Extension Cnet I F Module XBL C41A XBL C21A ...