Po
sit
io
n
in
g
Chapter 8 Functions
8-87
8.2.17 Start of Positioning
In case of stop in action of dynamic positioning, can positioning by restart. Three Starting types are general start,
Simultaneous start, point operation. Operating signal is have to “OFF”, when it start.
(1) Direct start
(a) Do not use operating data, directly input positioning data by auxiliary data and perform positioning control.
(b) Setting auxiliary data of direct start.
Setting item
Contents
Target position
Set target position of control.
Operating speed
Set operating speed of control.
Dwell time
Set dwell time (ms) that it is from positioning to outputting signal of positioning. (0~65535)
M code
Set for performing auxiliary action which is depending on set control.(0~65535)
Acceleration time
No.
Set acceleration time number for acceleration. (No.1 ~ No.4)
Reduction time
No.
Set reduction time number for reduction. (No.1 ~ No.4)
Coordinate
Set coordinate about target position of set control.(absolute, relative)
Control method
When command of converting position/speed is not inputted and only operated by
positioning control, set dwell time (ms) that it is from positioning to outputting signal of
positioning.
(0:Positioning, 1:Speed control, 2:Feed control)
Note
Direct start only can use when it is shortened operation. In case that Interpolation operation, use indirect starts.
(2) Indirect Start
(a) Start control of positioning by designating step number of operation data which was saved in positioning module.
(b) Setting auxiliary data of indirect start
Setting item
Contents
Operation step
Set step number of operation data what you need operating.(0 or 1 ~ 400)
Note
Set ‘O’ operation step of Indirect start and carry out command of indirect start. And then start operation data which
was saved in step number.
Summary of Contents for XBE-DC08A
Page 124: ...Main Chapter 1 Configuration and Operation Mode of Programs 1 27 1 Memory block diagram ...
Page 504: ...Position Chap 6 Commands 6 61 6 11 Function blocks related to Servo Drive ...
Page 644: ...Positioning Chapter 8 Functions 8 91 ...
Page 727: ...Positioning Chapter 9 Positioning Error Information Solutions 9 13 ...
Page 1207: ...Appendix 2 Dimension App2 2 2 Analog Type XEC DN32UA ...
Page 1209: ...Appendix 2 Dimension App2 4 XBE DC08A XBE DC16A XBE TN08A XBE TN16A XBE DR16A XBE RY08A ...
Page 1210: ...Appendix 2 Dimension App2 5 4 Extension Cnet I F Module XBL C41A XBL C21A ...