Chapter 6 Built-in PID Function
6-45
6.7.3 Stand-alone Operation After PID Auto-tuning
Here, with example, it explains how to execute PID control followed by PID auto-tuning.
(1) PID auto-tuning parameter setting
▪ PID auto-tuning parameters are set as same as examples of 6.4.2 Example of PID Auto-tuning.
(2) Setting parameters of A/D input module and D/A output module
▪ Set the parameters of A/D input module and D/A output module as same as the example in 6.4.2 Example of PID
Auto-tuning.
(3) PID parameter setting
(a) If double-clicking Parameter – Built-in Parameter – PID – PID Parameter, it shows the built-in PID parameter setting
window as seen in Figure 6.26.
[ Figure 6.26 Auto-tuning parameter setting window ]
(b) Set each parameter and click OK.
In the example, Loop 0 is set as follows.
•
RUN mode: automatic
- Set as automatic in order that PID control is executed as the built-in PID operation outputs MV.
•
RUN direction: forward
- Since in the system, water level is going up as MV increases and pump’s rotation velocity increases, it should
be set as forward operation.
•
PWM Output: disabled
- In the example, auto-tuning using PWM is not executed. Therefore, PWM output is set as disabled.
Summary of Contents for XBE-DC08A
Page 124: ...Main Chapter 1 Configuration and Operation Mode of Programs 1 27 1 Memory block diagram ...
Page 504: ...Position Chap 6 Commands 6 61 6 11 Function blocks related to Servo Drive ...
Page 644: ...Positioning Chapter 8 Functions 8 91 ...
Page 727: ...Positioning Chapter 9 Positioning Error Information Solutions 9 13 ...
Page 1207: ...Appendix 2 Dimension App2 2 2 Analog Type XEC DN32UA ...
Page 1209: ...Appendix 2 Dimension App2 4 XBE DC08A XBE DC16A XBE TN08A XBE TN16A XBE DR16A XBE RY08A ...
Page 1210: ...Appendix 2 Dimension App2 5 4 Extension Cnet I F Module XBL C41A XBL C21A ...