Spe
ci
al
Chapter 1 Embedded Analog
1-8
(2) DC 0 ~ 5V Output range
Digital value
Analog output voltage (V)
-0.06
0
1.25
2.5
3.75
5
5.059
Unsigned value
(-192 ~ 16,191)
-192
0
4,000
8,000
1,2000
16,000
16,191
Signed value
(-8,192 ~ 8,191)
-8,192
-8,000
-4,000
0
4,000
8,000
8,191
Precise value
(-60 ~ 5,059)
-60
0
1,250
2,500
3,750
5,000
5,059
Percentile value
(-120 ~ 10,119)
-120
0
2,500
5,000
7,500
10,000
10,119
(3) DC 0 ~ 10V Output range
Digital input
Analog output voltage (V)
-0.12
0
2.5
5
7.5
10
10.119
Unsigned value
(-192 ~ 16,191)
-192
0
4,000
8,000
12,000
16,000
16,191
Signed value
(-8,192 ~ 8,191)
-8,192
-8,000
-4,000
0
4,000
8,000
8,191
Precise value
(-120 ~ 10,119)
-120
0
2,500
5,000
7,500
10,000
10,119
Percentile value
(-120 ~ 10,119)
-120
0
2,500
5,000
7,500
10,000
10,119
(4) DC -10 ~ 10V Output range
Digital input
Analog output voltage (V)
-10.24
-10
-5
0
5
10
10.239
Unsigned value
(-192 ~ 16,191)
-192
0
4,000
8,000
12,000
16,000
16,191
Signed value
(-8,192 ~ 8,191)
-8,192
-8,000
-4,000
0
4,000
8,000
8,191
Precise value
(-10,240 ~ 10,239)
-10,240
-10,000
-5,000
0
5,000
10,000
10,239
Percentile value
(-120 ~ 10,119)
-120
0
2,500
5,000
7,500
10,000
10,119
Summary of Contents for XBE-DC08A
Page 124: ...Main Chapter 1 Configuration and Operation Mode of Programs 1 27 1 Memory block diagram ...
Page 504: ...Position Chap 6 Commands 6 61 6 11 Function blocks related to Servo Drive ...
Page 644: ...Positioning Chapter 8 Functions 8 91 ...
Page 727: ...Positioning Chapter 9 Positioning Error Information Solutions 9 13 ...
Page 1207: ...Appendix 2 Dimension App2 2 2 Analog Type XEC DN32UA ...
Page 1209: ...Appendix 2 Dimension App2 4 XBE DC08A XBE DC16A XBE TN08A XBE TN16A XBE DR16A XBE RY08A ...
Page 1210: ...Appendix 2 Dimension App2 5 4 Extension Cnet I F Module XBL C41A XBL C21A ...