Chapter 2 Built-in Cnet communication
2-63
B
u
ilt
-in
C
omm
3) Continuous writing of device (W(w)SB)
This is a function that directly specifies PLC device memory and continuously writes data from specified address as
much as specified length.
Request format
Format
name
Heade
r
Station
No.
Command
Comman
d type
Device
Length
Device name
Number
of data
Data
Tail
Frame
check
Frame
(Example)
ENQ
H10
W(w)
SB
H06
%MW100
H02
H11112222
EOT
BCC
ASCII
value
H05
H3130
H57(77)
H5342 H3036
H254D5731303
0
H3032 H3131313132323232 H04
•
Number of data specifies the number according to the type of device. Namely, if the data type of device is WORD, and
number of data is 5, it means that 5 WORDs should be written.
•
Number of data can be used up to 120Bytes (60 Words).
Item
Description
BCC
When command is lowercase(r), only one lower byte of the value resulted by adding 1 Byte
each to ASCII values from ENQ to EOT is converted into ASCII and added to BCC.
Device
Length
(Name length of
variable)
This indicates the number of name's characters that means device, which is allowable up to
16 characters. This value is one of ASCII converted from hex type, and the range is from
H01 (ASCII value: 3031) to H10 (ASCII value: 3130).
Device
Address to be actually read. This must be ASCII value within 16 characters, and in this
name, digits, upper/lower case, and '%' only are allowable to be entered.
XGB Response format (ACK response)
Format name
Header
Station No.
Command
Command type
Tail
Frame check
Frame (Example)
ACK
H10
W(w)
SB
ETX
BCC
ASCII value
H06
H3130
H57(77)
H5342
H03
Item
Description
BCC
When command is lowercase(r), only one lower byte of the value resulted by adding 1 Byte each
to ASCII values from ACK to ETX is converted into ASCII and added to BCC, and sent.
Note
Summary of Contents for XBE-DC08A
Page 124: ...Main Chapter 1 Configuration and Operation Mode of Programs 1 27 1 Memory block diagram ...
Page 504: ...Position Chap 6 Commands 6 61 6 11 Function blocks related to Servo Drive ...
Page 644: ...Positioning Chapter 8 Functions 8 91 ...
Page 727: ...Positioning Chapter 9 Positioning Error Information Solutions 9 13 ...
Page 1207: ...Appendix 2 Dimension App2 2 2 Analog Type XEC DN32UA ...
Page 1209: ...Appendix 2 Dimension App2 4 XBE DC08A XBE DC16A XBE TN08A XBE TN16A XBE DR16A XBE RY08A ...
Page 1210: ...Appendix 2 Dimension App2 5 4 Extension Cnet I F Module XBL C41A XBL C21A ...