ru-Parameter
200Fh
1
-
-
247
0
ru.15 Output terminal state
Display of the currently set external and internal digital outputs. According to following table a certain decimal value is
given out for each digital output. If several outputs are set then the sum of their decimal values is displayed.
Bit -No.
Decimal value
Output
Terminal
0
1
D1 (transistor output)
X2.8
1
2
D2 (transistor output)
X2.9
2
4
Out 3 (output relay)
X2.20 , 21 , 22
4
16
Out A (internal output A)
none
5
32
Out B (internal output B)
none
6
64
Out C (internal output C)
none
7
128
Out D (internal output D)
none
ru.12 Peak DC voltage
ru.12 allows the detection of short-time voltage rises within an operating cycle. For that the highest detected value of
ru.11 is stored in ru.12. The peak value memory is cleared by pressing the keys UP or DOWN or by bus by writing any
chosen value to the address of ru.12. The disconnection of the inverter also results in a clearing of the memory.
ru.14 Input terminal state
Display of the actual triggered digital inputs. Whether the input is inverted or the internal acceptance takes place
through edge triggering or strobe is irrelevant for the display. According to following table a certain decimal value is
given out for each digital input. If several inputs are triggered then the sum of their decimal values is displayed.
Bit -No.
Decinal value
Input (standard program)
Terminal
0
1
ST (control release)
X2.1
1
2
I4 (Reset)
X2.2
2
4
I5 (rotation Forward)
X2.3
3
8
I6 (rotation Reverse)
X2.4
4
16
I1 (prog. input 1)
X2.5
5
32
I2 (prog. input 2)
X2.6
6
64
I3 (prog. input 3)
X2.7