In CP.32 you can select whether the inverter operates open-loop or closed loop.
Adjustment Range:
0…1
Resolution:
1
Factory setting:
0
Customer setting:
________
0
=
open-loop
(U/f-curve)
1
=
closed-loop (field-oriented control)
During open-loop operation the torque limits, levels and displays do not have a function.
All parameters, that access these values, either do not have a function or have a
restricted function. This is described in the individual parameters.
Speed Regulation on/off
Boost
The voltage increase for the lower speed range is adjusted with the boost, which
results in a higher torque in the lower range.
During closed-loop operation this
parameter does not have a function!
Adjustment Range:
0…25,5
%
Resolution:
0,1
%
Factory setting:
2
%
Customer setting:
________
%
Caution !
Only switch over when control release is
open !
Torque jumps may occur if not observed.
100
CP.33
f [Hz]
CP.28
U
A
[%]
When the motor is driven during continuous operation at a slow
speed and the voltage is too high, the motor may overheat!