
6
1
Name: Basis
KEB COMBIVERT F4-F
6
16.03.99
Fucntional Description
©
KEB Antriebstechnik, 1999
All Rights reserved
Chapter
Section
Page
Date
ru-Parameter
3. Fault signals
The reaction of the drive to the fault signals listed below (abnormal stopping) can be determined with parameter Pn.20
and Pn.23...Pn.26:
Display
Bus
Meaning
A.EF
90
Abnormal Stopping
- The signal for an external fault is given to a programmable digital
input.
(reaction of the drive see parameter Pn.20)
A.buS
93
Abnormal Stopping
- The adjusted Watchdog-time (parameter ud.8) of the serial
communication was exceeded.
(reaction of the drive see parameter Pn.23)
A.PrF
94
Abnormal Stopping
- At setpoint direction forward terminal F (rotation release forward)
Prohibited Rotation
is not active.
Forward
(reaction of the drive see parameter Pn.24)
A.Prr
95
Abnormal Stopping
- At setpoint direction reverse terminal R (rotation release reverse)
Prohibited Rotation
is not active.
Reverse
(reaction of the drive see parameter Pn.24)
A.dOH
96
Abnormal Stopping
- The temperature monitoring of the motor has tripped and the pre-
Drive Overheat
warning time (Pn.16) is active.
(reaction of the drive see parameter Pn.25)
A.OH
99
Abnormal Stopping
- The temperature monitoring of the frequency inverter has tripped
Overheat
and the prewarning time (10 s) is active.
(reaction of the drive see parameter Pn.26)