KEB Antriebstechnik, 1998
All rights reserved
Chapter
Section
Page
Date
2
1
KEB COMBIVERT F4-F
6
Name: Basis
11.12.98
Product Description
Summary
The following technical specifications refer to 2-/4-pole standard motors. In case of
different pole numbers the frequency inverter must be dimensioned for the rated
motor current. With regard to special or medium frequency motors, please contact
KEB.
Site altitude max. 2000 m. For altitudes of 1000 m or more above N.N. a power reduction
of 1 % per 100m must be taken into account.
1) The statement counts only for frequency inverters with internal braking transistor (see „2.1.4 Type Code“).
Inverter Size
07
12
13
14
15
16
Output nominal power
[kVA]
1,6
6,6
8,3
11
17
23
Max. rated motor power
[kW]
0,75
4
5,5
7,5
11
15
Output nominal current
[A]
4
16,5
24
33
48
66
Max. short-time current
[A]
7,2
24,8
36,5
49,5
72
99
OC-tripping current
[A]
8,8
29,7
43
59
88
119
Nominal input current
[A]
8
4,4
33
18,1
26,5
36
53
73
Housing size
D
D
E
E
G
G
H
H
Rated operating frequency
[kHz]
16
8
16
16
16
16
Max.operating frequency
[kHz]
16
8
16
16
16
16
Power loss at nominal operating
[W]
65
210
220
280
430
550
Stall current at 8kHz
[A]
-
-
16,5
19
-
-
-
Stall current at 16kHz
[A]
-
-
-
-
8,6
-
-
-
Max. heat sink temperatureT
OH
[°C]
85
73
90
90
90
90
Max. permissible mains fuse (inert)
[A]
20
10
35
25
35
50
80
80
Line cross section
[mm²]
2,5
1,5
6
4
6
10
25
25
Min. braking resistor
1)
[
Ω
]
56
21
16
13
5,6
5,6
Typ. braking resistor
1)
[
Ω
]
100
28
22
16
13,6
8,8
Max. braking current
[A]
7
19
29
29
70
70
Tightening torque for terminals
[Nm]
0,5
0,5
1,2
Mains voltage
[V]
305...500 +/-0 (400V Nominal voltage)
Phases
1
3
1
3
3
3
3
3
Mains frequency
[Hz]
50 / 60 +/- 2
Output voltage
[V]
3 x 0...U Mains
Output frequency
[Hz]
see control board
Shielded motor line length
[m]
30
30
100
Storage temperature
[°C]
-25...70 °C
Operating temperature
[°C]
-10...45 °C
Model / protective system
IP20
Relative humidity
max. 95% without condensation
Tested in accordance with...
EN 61800-3
Climatic category
3K3 in accordance with EN 50178
2.1.5 Validity of
Specifications
2.1.6 Unit Sizes 230V-Class