Functional Description
Parameter Sets
Remedy
Open control release or activate another
parameter set.
Open control release or trigger error.
Change either source or target set.
Select valid value (0…7) as target set.
Fig. 6.8.3.a Principle of parameter set selection
Error message „nco“
If error message „nco“ is displayed, it can have the following causes:
Cause
Attempt of copying the default set
(def) into the just active set.
During initialization (init) the control
release was not disabled.
Source and target set are identical.
The current set (A) is selected as
target set.
Adjustment of source and
target set by keyboard
(Fr.1 / Fr.9)
At bus operation two parameters are responsible for the copying of parameter sets.
Fr.9 defines the target set. Fr.1 defines the source parameter set and starts the copying
process. These parameters are not visible by way of keyboard.