Actual inverter utilization
Display of the actual load related to the rated current of the inverter. Only positive values are displayed, thus a
differentiation between motoric and generatoric operation is not possible.
ru. 8
Peak inverter utilization
ru.8 allows the detection of short-time peak loads during an operating cycle. For that the highest detected value of ru.7
is stored in ru.8. The peak value memory is cleared by pressing the keys UP or DOWN or by bus by writing any chosen
value to the address of ru.8. The disconnection of the inverter also results in a clearing of the memory.
ru.9
Apparent current
Display of actual apparent curent. The maximum values depend on the size of the inverter.
ru.10 Active current
Display of the torque-forming active current. Precondition is the input of the motor data into dr.0...dr.4. The maximum
values depend on the size of the inverter. With regard to limitations of the accuracy refer to ru.2. In controlled operation
(CS.23 = 0) the display always shows 0.0 A.
unit-dependent
unti-dependent
Display of actual DC-link voltage. Typical values are for
normal operation: 230V-class approx. 300-330V
in case of fault (E.OP):
230V-class approx.390V
400V-class approx. 530-620V
400V-class approx.800V
ru.11 Actual DC voltage