Function Analog Input REF2
0
no function
1
adds to the setpoint (has no influence on the Jogging operation) 1 0
V = CP.10
2
works as a multiplier for parameter CP.12 (P-factor of the speed
controller)
10 V = gain 1
3
works as a multiplier for parameter CP.13 (I-factor of the speed
controller)
10 V = gain 1
4
works as a multiplier for parameter CP.12 + CP.13 (total gain of the speed
cotnroller)
10 V = gain 1
5
works as a multiplier for parameter CP.9 (torque limit)
10 V = gain 1
6
torque control; only available in the application mode
In CP.36 you can adjust on which parameter the 2nd analog input REF2 should work
(X2.16 / X2.17).
During open-loop operation values 2; 3; 4 and 5 do not have a
function !
Adjustment range:
0…6
Resolution:
1
Factory setting:
0
Customer setting:
________