6.7.6
Used Parameters
Fr.0
2700h
✔
✔ ✔
-2
7
1
0
not by bus
Fr.1
2701h
✔
-
-
-2
7
1
0
not by keyboard
Fr.2
2702h
✔
-
✔
0
3
1
0
-
Fr.3
2703h
✔
-
✔
0
255
1
0
-
Fr.4
2704h
✔
-
✔
0
7
1
0
-
Fr.5
2705h
✔
✔
-
0,000
10,000 s
0,001 s
0,000
-
Fr.6
2706h
✔
✔
-
0,000
10,000 s
0,001 s
0,000
-
Fr.9
2709h
✔
-
-
-1
7
1
0
not by keyboard
6.7.5
Parameter Set ON
and OFF Delay
(Fr.5, Fr.6)
With these parameters a time of 0...10s can be adjusted,
- with which the activation of a new set is delayed (Fr.5)
- with which the deactivation of the old set is delayed (Fr.6)
At set changeover the turn-off time of the old set and the turn-on time of the new set
are added up.
Fig. 6.8.5
ON and OFF delay
Example
Set
Fr.5
Fr.6
0
0 s
0 s
1
2 s
0 s
2
0 s
1 s
3
2 s
2 s
1:
ON delay set 3 of 2s
2:
OFF delay set 3 of 2s
3:
OFF delay set 2 of1s +
ON delay set 1 of 2 s
4:
Immediate changeover as no delay-time is adjusted
5:
OFF delay set 2 of 1s +
ON delay set 3 of 2s
6:
OFF delay set 3 of2s
Set 1
Set 3
Set 2
Set 1
Set 3
Set 2
Set 0
Set 0