Name: Basis
KEB COMBIVERT F4-F
16.03.99
Functional Description
Set Value and Ramp Adjustment
Chapter
Section
Page
Date
©
KEB Antriebstechnik, 1999
All Rights reserved
SP.4
SP.5
SP.6 (SP.4)
SP.7 (SP.5)
SP.4
SP.5
SP.6 (SP.4)
SP.7 (SP.5)
SP.4
SP.5
SP.6 (SP.4)
SP.7 (SP.5)
6.4.4
Setpoint Calculation
Setpoint setting : -10V ... +10V (REF1)
At
SP.0 = 0 and 1
negative setpoint values are internally set to 0 and
the direction of rotation is adjusted digital by way of parameter SP.3
or terminals forward and reverse.
At
SP.0 = 2
the direction of rotation is defined through the sign of the
setpoint.
Setpoint setting : -9999,5 rpm ... +9999,5 rpm (parameter SP.1)
At
SP.0 = 3 and 4
negative setpoint values are internally set to 0 and
the direction of rotation is adjusted digital by way of parameter SP.3
or terminals forward and reverse.
At
SP.0 = 5
the direction of rotation is defined through the sigh of the
setpoint.
Attention!
Speed values up to +/- 9999,5 rpm can be adjusted,
however, internally the calculation is done only with the
adjusted maximum speed values.
+n [U/min]
-n [U/min]
Maximum speed
Minimum speed
Minimum speed
Maximum speed
+n [U/min]
Maximum speed
Minimum speed
Minimum speed
Maximum speed
Value of
SP.7 (SP.5) ^
= -100%
Value of
SP.5 ^
= 100%
SP.1 [U/min]
Anlaog setpoint setting
Absolute digital setpoint setting
Setpoint setting : -100%...+100% (parameter SP.2)
At
SP.0 = 6 and 7
negative setpoint values are internally set to 0 and
the direction of rotation is adjusted digital by way of parameter SP.3
or terminals forward and reverse.
At
SP.0 = 8
the direction of rotation is defined through the sign of the
setpoint.
percentual digital setpoint setting
REF1 [V]
REF1 [V]
10V
100
%
-10V
-100 %
+n [U/min]
-n [U/min]
Maximum speed
Minimum speed
Minimum speed
Maximum speed
SP.2 [%]
SP.2 [%]
100
%
-100 %
SP.1 [U/
min]
Fig. 6.4.4
Setpoint analog
Fig. 6.4.5
Setpoint digital absolute
Fig. 6.4.6
Setpoint digital percentual
-n [U/min]