Functional Description
Digital In- and Outputs
Terminal
Name
Function
Decimal value do.0, do.25 u. ru.15
X2.8
Out1
transistor output 1
1
X2.9
Out2
transistor output 2
2
X2.20...22
Out3
relay output
4
-
-
reserved
-
-
Out A
internal output
16
-
Out B
internal output
32
-
Out C
internal output
64
-
Out D
internal output
128
6.3.17 Inverting of Out-
puts (do.0)
As shown in Fig. 6.3.16 with parameter do.0 the outputs can be inverted. The parameter
is bit-coded, i.e. according to following table the value belonging to the output must
be entered. If several outputs shall be inverted add up the sum.
6.3.18 Output Terminal
Status (ru.15)
The output terminal status indicates the logic condition of the digital outputs. At that it
is irrelevant whether the output is set based on the conditions or through inverting. If
an output is set the corresponding decimal value according to the above table is
displayed. If several outputs are set then the sum of the decimal value is indicated.
Example:
Out1 and Out3 to be inverted
➭
1+4 =
5