
4
3
KEB COMBIVERT F4-F
12
Name: Basis
15.12.98
CP - Parameter
©
KEB Antriebstechnik, 1998
All Rights reserved
Operation
Chapter
Section
Page
Date
Value
Error / Status
Response of the drive
massage
0
E.EF
modulation immediately switched off
!
To restart remove error and
activate
Reset !
1
A.EF
quick stop / modulation switched off after speed 0 is
reached
!
To restart remove error and
activate
Reset !
2
A.EF
quick stop / holding tourqe at speed 0
!
To restart remove error and
activate
Reset !
3
A.EF
modulation immediately switched off
!
Automatic restart
, when error is no longer present
!
4
A.EF
quick stop / modulation switched off after speed 0 is
reached
!
Automatic restart
, when error is no longer present
!
5
A.EF
quick stop / holding tourqe at speed 0
!
Automatic restart
, when error is no longer present
!
6
none
no effect on the drive
!
Fault is ignored
!
Behaviour at External Fault
This parameter determines how the drive reacts to an external error (digital Input I3).
Adjustment Range:
0…6
Resolution:
1
Factory setting:
0
Customer setting:
________
Note:
ENTER-Parameter
Quick stop
⇒
⇒
⇒
⇒
⇒
deceleration at the torque limit (CP.9)