Name: Basis
08.03.99
Chapter
Section
Page
Date
©
KEB Antriebstechnik, 1999
All Rights reserved
Functional Description
Parameter Sets
Input-coded set selection
ID
IB
I4
I2
I1
Set
0
0
0
0
0
0
0
0
0
0
1
1
0
0
0
2
0
2
0
0
3
0
0
3
0
4
0
0
0
4
5
0
0
0
0
5
5
0
3
0
0
3
5
0
3
0
1
1
Fig. 6.8.3.c Input-coded parameter set selection
For bit-coded set selection
-
maximal 7 of the internal or external inputs may be programmed for set selection
(0…7 sets) in order to avoid set selection errors.
-
the lowest of the selected inputs has priority
(I1 > I2 > I3 > I4 > I5 > I6 > IA > IB > IC > ID)
Example 1: Set 0…5 shall be selected with 5 inputs (I1, I2, I4, IB und ID).
1.)
Adjust parameter di.3, di.4, di.6, di.8 and di.10 to value „1“
2.)
Parameters di.5, di.7 and di.9 must be set to
≠
1
3.)
Adjust Fr.2 to value „3“ (set selection input-coded by way of terminal strip)
6.7.4
Locking of Para-
meter Sets
Parameter sets that shall not be selected can be locked with Fr.3. If one of the locked
sets is selected, the inverter switches off with set selection error (E.SEt).
Value
Locked set
Example
1
0
-
2
1
-
4
2
4
8
3
-
16
4
-
32
5
32
64
6
-
128
7
-
Set 2 and set 5 lcoked Sum
36
Parameter set lock (Fr.3)
Set 0
Set 1
Set 2
Set 3
Set 4
Set 5
I1
I2
I4
IB
ID