15
ANTRIEBSTECHNIK
6
5
15
KEB COMBIVERT F4-F
Name: Basis
11.05.99
6
Section
Page
Date
©
KEB Antriebstechnik, 1999
All Rights reserved
Chapter
Functional Description
Motor Data and Controller Adjustment
There are two controlled conditions at torque control – torque and speed.
Parameter An.13 (Aux-function)must be adjusted with value „6“ to activate the torque
control. The function of the analog inputs is changed as follows:
REF2 (X2.16 / X2.17) =>
Input of the speed
10 V is correspond to the max. speed SP.5
(negative values are interpreted with 0)
REF1 (X2.14 / X2.15) =>
Torque set value
±10V is correspond to the torque limit CS.6
(the sign determines the direction of rotation)
If the torque limit is higher than the max. torque (see
characteristic curve picture 6.5.14.b), the torque set
value is limited to the max. torque. Scan time 128 ms.
Torque control is only
available when the control
mode is disconnected.
(Pc.0 = 0).
-10V
10V
-5V
5V
Torque
Max. torque dr.10
Torque limit CS.6
REF1
Max. torque dr.10
Torque limit CS.6
6.5.18 Torque input via REF1
6.5.18 Torque Control