11
1
4
Name: Basis
KEB COMBIVERT F4-F
05.01.99
Chapter
Section
©
KEB Antriebstechnik, 1998
All Rights reserved
Page
Date
Networks
Network Hardware
5
2
4 3
1
9 8 7 6
11.1.3 Interface- and
Bus-Operator
Integrated into the Interface Operator (00.F4.010-1009) is an isolated RS232/RS485
interface. The RS232-interface is not applicable for the Bus-Operator (00.F4.010-
7009). The telegram structure is compatible to protocol DIN 66019 and ANSI X3.28, sub
catagory 2.5, A2, A4 and ISO 1745.
RS232/RS485
PE-Connection
PIN
RS485
Signal
Significance
1
–
–
reserved
2
–
TxD
transmitter signal /RS232
3
–
RxD
receive signal /RS232
4
A'
RxD-A
receive signal A/RS485
5
B'
RxD-B
receive signal B/RS485
6
–
VP
supply voltage -Plus +5V (I
max
=10mA)
7
C/C'
DGND
data reference potential
8
A
TxD-A
transmitter signal A/RS485
9
B
TxD-B
transmitter signal B/RS485