KEB COMBIVERT F4-F
Name: Basis
17.06.99
6
Section
Page
Date
©
KEB Antriebstechnik, 1999
All Rights reserved
Chapter
Functional Description
Positioning Module
In the case of relative positioning (e.g. clock drive) the software limit switches can be
deactivated (factory setting). Following procedure must be carried out:
• Select position setting in revolutions Pc.1 = 3
• Adjust left software limit switch to negative upper range value
Pc.5 = -32768
Pc.6 = 0
• Adjust right software limit switch to positive upper range value
Pc.8 = 32767
Pc.9 = 65535
The behaviour at tripping of the faults ESLF and E.SLr is defined with Pn.20 according
to following table:
Deactivation of software limit
switch
Pn.24 Display Reaction
Restart
0
E.SLx
Immediate disabling of modulation
1
A.SLx
Quick stopping / disabling of modulation
after reaching speed 0
2
A.SLx
Quick stopping / holding torque at speed 0
3
A.SLx
Immediate disabling of modulation
4
*1
A.SLx
Quick stopping / disabling of modulation
after reaching speed 0
5
*1
A.SLx
Quick stopping / holding torque at speed 0
6
keine
No effect on the drive;
!Fault is being ignored!
Remove fault;
Actuate reset
Automatic reset, if
the fault is no longer
present
- inapplicable -
Reaction to limit switch (Pn.24)
*1
Caution, the drive can run out of the limit switches, without stopping the
positioning!
It is necessary for the values, to adjust the emergency stop/braking torque (Pn.60),
the positioning speed and the lug lenght (or the diameter at the initiator) of the
limit switch, that the drive stops at the limit switch.