Figure 3-2
Direction of heat dissipation
3.2.2 Temperature and Humidity Requirements
To ensure continued safe and reliable equipment operating, install or position the system in a
well-ventilated, climate-controlled environment.
l
Use temperature control devices all year long in any climates.
l
In dry areas, use humidifiers to ensure ambient humidity.
l
In humid areas, use dehumidifiers.
Table 3-1
Temperature and humidity requirements in the equipment room
Item
Description
Temperature
5°C to 40°C (41°F to 104°F)
Relative humidity (RH, non-condensing)
8% to 90%
3.2.3 Cabinet Requirements
The cabinet must meet the following requirements:
l
A standard 19-inch cabinet with a depth of more than 1000 mm (39.37 in.).
l
Complies with International Electrotechnical Commission 297 (IEC 297).
RH2288 V3 Server
User Guide
3 Installing and Removing the Server
Issue 32 (2019-03-28)