Item
Specifications
Maximum altitude
3048 m (9999.88 ft)
l
For altitudes above 900 m (2952.72 ft), the highest operating
temperature decreases by 1°C (1.8°F) for every increase of 300 m
(984.24 ft) in altitude.
l
At an altitude of over 3000 m (9842.4 ft), only Titanium PSUs can
be used.
l
HDDs cannot be used at an altitude of over 3000 m (9842.4 ft).
Acoustic noise
The data listed in the following is the declared A-weighted sound
power levels (LWAd) and declared average bystander position A-
weighted sound pressure levels (LpAm) when the server is operating
in a 23°C (73.4°F) ambient environment. Noise emissions are
measured in accordance with ISO 7779 (ECMA 74) and declared in
accordance with ISO 9296 (ECMA 109).
l
Idle:
–
LWAd: 5.1 Bels
–
LpAm: 35.1 dBA
l
Operating:
–
LWAd: 6.1 Bels
–
LpAm: 45.1 dBA
NOTE
The actual sound levels generated during server operating vary depending on
the server configuration, load, and ambient temperature.
Corrosive air
pollutant
l
Maximum corrosion rate of the copper test piece: 300 Å/month (in
compliance with the ANSI/ISA-71.04-2013 gaseous corrosion
level G1)
l
Maximum corrosion rate of the silver test piece: 200 Å/month
Particulate
pollutant
l
The ISO14664-1 Class 8 requirements are met.
You are advised to ask a professional organization to monitor
particulate pollutants in the equipment room.
l
There is no explosive, conductive, magnetic, or corrosive dust in
the equipment room.
Power
consumption
The power consumption changes depending on the server
configuration. Use the
Huawei Server Power Calculator
calculate the power.
RH2288 V3 Server
User Guide
2 Overview
Issue 32 (2019-03-28)