The meanings of the identifiers on the inner sides of the guide rails are as follows:
l
F/L: The guide rail is to be installed on the left side of the cabinet, and the end marked
with the identifier is the front end of the guide rail.
l
F/R: The guide rail is to be installed on the right side of the cabinet, and the end marked
with the identifier is the front end of the guide rail.
The requirements for cabinet dimensions are listed as follows:
l
For a 1200 mm (47.24 in.) deep cabinet, the minimum internal width of the cabinet must
be greater than 473 mm (18.62 in.); the distance between the front mounting bar and the
front inner side must be 65 mm (2.56 in.) to 115 mm (4.53 in.); the distance between the
front and rear mounting bars must be 689 mm (27.13 in.) to 929 mm (36.57 in.). The
recommended guide rail is 21240817, which does not occupy extra space.
l
For a 1100 mm (43.31 in.) deep cabinet, the minimum internal width of the cabinet must
be greater than 473 mm (18.62 in.); the distance between the front mounting bar and the
front inner side must be 65 mm (2.56 in.) to 115 mm (4.53 in.); the distance between the
front and rear mounting bars must be 689 mm (27.13 in.) to 929 mm (36.57 in.). The
recommended guide rail is 21240817, which does not occupy extra space.
l
For a 1000 mm (39.37 in.) deep cabinet, the minimum internal width of the cabinet must
be greater than 449 mm (17.68 in.); the distance between the front mounting bar and the
front inner side must be 65 mm (2.56 in.) to 115 mm (4.53 in.); the distance between the
front and rear mounting bars must be 500 mm (19.69 in.) to 858 mm (33.78 in.). The
recommended guide rail is 21241598, which occupies 1U space.
Figure 3-14
Minimum internal width of the cabinet and the distance between the front and
rear mounting bars