5–38
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
DEVICE
CHAPTER 5: DEVICE, SYSTEM, INPUT AND OUTPUT SETPOINTS
Remote Modbus
Device
The Remote Modbus Device describes a device within the same network as the
8 Series device and the poll mode of operation for retrieving the data. The 8 Series device
acts as a Modbus Master and initiates Modbus requests to the Modbus slave at a defined
poll interval or per trigger.
Path:
Device > Communications > Remote Modbus Device > Device 1
DEVICE NAME
Range: 13 Alphanumeric Characters
Default: BSG3
The Remote Modbus Device currently supports the Powell BriteSpot Thermal Monitoring
device (BSG3). The 27 analog and 27 digital operands that are available in the device are
supported and are pre-configured in the default settings file. The data defined for BSG3
are described in the 8 Series Protection Relay Platform Communications guide.
IP ADDRESS
Range: Standard IPV4 network address format
Default: 0.0.0.0
SLAVE ADDRESS
Range: 1 to 254 in steps of 1
Default: 254
MODBUS PORT
Range: 0 to 10000 in steps of 1
Default: 502
POLL RATE
Range: OFF, 3 to 120 minutes in steps of 1
Default: 3 minutes
TRIGGER
Range: Any FlexLogic operand
fault: Off
Summary of Contents for Multilin 850
Page 10: ...VIII 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL ...
Page 135: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 41 ...
Page 151: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 57 ...
Page 153: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 59 ...
Page 439: ...CHAPTER 7 MONITORING FUNCTIONS 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 7 19 ...
Page 644: ...11 20 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 11 METERING ...