3–54
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
SOFTWARE INTERFACE
CHAPTER 3: INTERFACES
Transient Recorder
(Waveform Capture)
The EnerVista 8 Series Setup software can be used to capture waveforms (or view trace
memory) from the relay at the instance of a pickup, trip, alarm, or other condition.
•
With EnerVista 8 Series Setup software running and communications established,
select the
Records > Transients > Transient Records
menu item to open the
Transient Recorder Viewer window.
•
Click on
Trigger Waveform
to trigger a waveform capture.
•
To view the captured waveforms, click on the
Launch Viewer
button. A detailed
Waveform Capture window appears as shown below.
•
Click on the
Save
button to save the selected waveform to the local PC. A new window
appears, requesting the file name and path. One file is saved as a COMTRADE file, with
the extension "CFG." The other file is a "DAT" file, required by the COMTRADE file for
proper display of waveforms.
•
To view a previously saved COMTRADE file, click the
Open
button and select the
corresponding COMTRADE file.
Summary of Contents for Multilin 850
Page 10: ...VIII 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL ...
Page 135: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 41 ...
Page 151: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 57 ...
Page 153: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 59 ...
Page 439: ...CHAPTER 7 MONITORING FUNCTIONS 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 7 19 ...
Page 644: ...11 20 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 11 METERING ...