CHAPTER 9: FLEXLOGIC AND OTHER SETPOINTS
TESTING
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
9–27
FORCE LEDS
Range: Disabled, Enabled
Default: Disabled
When in test mode, and Force LEDs is “Enabled”, LED states and colors can be forced
from the
Setpoints > Testing > Test LEDs
menu, this will override the normal operation of
the LEDs. When in test mode, and Test LEDs is “Disabled”, the LED states and colors will
maintain their normal operation. Forcing of LEDs is not performed when the Simulation
State is “Disabled”.
Pre-Fault
This state is intended to simulate the normal operating condition of a system by replacing
the normal input parameters with programmed pre-fault values. For proper simulation,
values entered here must be below the minimum trip setting of any protection feature.
Voltage magnitudes and angles are entered as Wye values only. The voltage setpoints are
not available if the corresponding VT Bank PHASE VT CONNECTION setpoint is Delta.
Voltages are set in secondary VT units.
The CT and VT Bank availability is dependent on the installed Order Code options.
Path:
Setpoints > Testing > Simulation > Pre-Fault
J2 Prefault Van(Vbn,Vcn,Vx) Voltage:
Range: 0.00 to 300.00 V in steps of 0.01
Default: 0.00 V
J2 Prefault Van(Vbn,Vcn,Vaux) Angle:
Range: -359.9° to 0.0° in steps of 0.1
Default: 0.0°
J2 -LEA 1(2) Prefault Van(Vbn,Vcn) Voltage:
Range: 0.00 to 30.00 V in steps of 0.01
Default: 0.00 V
J2 -LEA 1(2)Prefault Van(Vbn,Vcn) Angle:
Range: -359.9° to 0.0° in steps of 0.1
Default: 0.0°
J1 Prefault Phase la(lb,lc):
Range: 0.000 to 46.000 x CT in steps of 0.001 x CT
Default: 0.000 x CT
Phase current magnitudes are entered as a multiple of the corresponding CT Bank
PHASE CT PRIMARY setpoint.
J1(K1) Prefault Phase lg:
Range:
For Ground CT: 0.000 to 46.000 x CT in steps of 0.001 x CT
For Sensitive Ground CT: 0.000 to 4.600 x CT in steps of 0.001 x CT
Default: 0.000 x CT
The ground current magnitude setpoint range is dependent on the ground CT type as
defined in the Order Code options. For Ground CT, the magnitude is entered as a multiple
of the corresponding CT Bank GROUND CT PRIMARY setpoint. For Sensitive Ground CT,
the magnitude is entered as a multiple of the corresponding CT Bank SENS GROUND CT
PRIMARY setpoint.
J1(K1) Prefault la(lb,lc,lg) Angle:
Range: -359.9° to 0.0° in steps of 0.1
Default: 0.0°
Summary of Contents for Multilin 850
Page 10: ...VIII 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL ...
Page 135: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 41 ...
Page 151: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 57 ...
Page 153: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 59 ...
Page 439: ...CHAPTER 7 MONITORING FUNCTIONS 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 7 19 ...
Page 644: ...11 20 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 11 METERING ...