5–90
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
INPUTS
CHAPTER 5: DEVICE, SYSTEM, INPUT AND OUTPUT SETPOINTS
Analog Inputs
The 8 Series relay can monitor any external quantity from the DcmA transducers such as
vibration, field current, pressure, tap position etc., using ‘Analog Inputs’. Any one of the
standard transducer output ranges: 0 to 1 mA, 0 to 5 mA, 0 to 10mA, 0 to 20 mA, or 4 to 20
mA can be connected to the Analog Input terminals. Polarity of these inputs must be
observed for proper operation. The analog input circuitry is isolated as a group with the
analog output circuitry and the RTD circuitry, only one ground reference is used for the
three circuits. Transducers limit this isolation to ±36 V with respect to the 8 Series safety
ground.
Depending upon the order code, the 8 Series relay supports one optional DC analog card.
The analog card has 4 analog inputs and 7 analog outputs. For each element, when the
measured analog input quantity exceeds the Pickup level for longer than the associated
time delay, the relay can be configured to cause an alarm, or trip. The element will drop
out only when the user programmed Dropout ratio has been met.
NOTE
NOTE:
The connected analog input is still read and displayed in METERING /ANALOG INPUTS if the
trip function or alarm function is set to “Disabled”, and the Analog Input is not Disabled.
Path
:
Setpoints > Inputs > Analog Inputs > Analog Input 1(X)
Settings
FUNCTION
Range: Disabled, Enabled
Default: Disabled
This setting enables or disables the Analog Input function.
NAME
Range: Any combination of 13 Characters
Default: Anlp 1
This setting allows the assignment of symbolic names to each analog input. The length
is limited to 13 characters.
UNITS
Range: Any combination of 6 Characters
Default: units
This setting allows the assignment of symbolic names to the engineering units. The
length is limited to 6 characters.
RANGE
Range: 0 to 1 mA, 0 to 5 mA, 0 to 10 mA, 0 to 20 mA, 4 to 20 mA
Default: 0 to 1 mA
This setting provides the selection for the analog input range.
MIN VALUE
Range: -500000 to 500000 units in steps of 1 unit
Default: 0
For the MINIMUM VALUE setpoint, enter the value which corresponds to the minimum
output value of the transducer. For example, if a temperature transducer which outputs
4 to 20 mA for temperatures 0 to 250°C is connected to the analog input, then enter “0”
for the MINIMUM VALUE. The relay then interprets 4 mA as representing 0°C.
Intermediate values between the minimum and maximum are scaled linearly.
Summary of Contents for Multilin 850
Page 10: ...VIII 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL ...
Page 135: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 41 ...
Page 151: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 57 ...
Page 153: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 59 ...
Page 439: ...CHAPTER 7 MONITORING FUNCTIONS 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 7 19 ...
Page 644: ...11 20 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 11 METERING ...