CHAPTER 7: MONITORING
FUNCTIONS
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
7–33
NEG VARHS PULSE INCREMENT
Range: 0.000 to 1000.000 MVARh in steps of 0.001 MVARh
Default: 10.000 MVARh
The setpoint specifies the positive VARhours threshold pulse increment after which the
output pulse and output operand are set.
NEG VARHS PULSE RELAY X
For details see
EVENTS
Range: Disabled, Enabled
Default: Enabled
TARGETS
Range: Disabled, Self-reset, Latched
Default: Self-Reset