
CHAPTER 8: CONTROL
BREAKER FAILURE (50BF)
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
8–29
Outputs
The outputs from the schemes are:
•
Re-trip of the protected breaker
•
FlexLogic operand that reports on the operation of the portion of the scheme where
high-set or low-set current supervision is used
•
FlexLogic operand that reports on the operation of the portion of the scheme where
52b status supervision is used only
•
FlexLogic operand that initiates tripping required to clear the faulted zone. The
Breaker Failure output can be sealed-in for an adjustable period
•
Target message indicating a failed breaker has been declared.
Setup
Path
:
Setpoints > Control > Breaker Failure > BF1(X) > BF1(X) Setup
FUNCTION
Range: Disabled, Retrip, Latched Alarm, Alarm, Configurable
Default: Disabled
When the
Retrip
function is selected and Breaker Failure is initiated (with re-trip current
supervision), the output relay #1 “Trip” operates but the “ALARM” LED does not turn on.
SIGNAL INPUT
Range: dependant upon the order code
Default: CT Bank 1-J1
PH RETRIP SUPERV PICKUP
Range: 0.050 to 30.000 x CT in steps of 0.001 x CT
Default: 1.000 x CT
The setpoint specifies the phase current Retrip level, which when exceeded after Breaker
Failure initiation, will Retrip its own breaker. The setting is set to detect the lowest
expected fault current on the protected circuit.
NTRL RETRIP SUPERV PICKUP
Range: 0.050 to 30.000 x CT in steps of 0.001 x CT
Default: 1.000 x CT
This setpoint specifies the neutral current Retrip level, which when exceeded after
Breaker Failure initiation, will Retrip its own breaker. The setting detects the lowest
expected fault current on the protected circuit. Neutral Retrip current supervision is used
to provide increased sensitivity.
SUPERVISION
Range: Current, 52b & Current, 52b
Default: Current
The setpoint specifies the type of supervision of the Breaker Failure element. There are
three options: current only, breaker status only, or both.
BREAKER CLOSED
Range: Off, Any FlexLogic operand
Default: Off
The setpoint selects the FlexLogic operand (auxiliary switch contact) to indicate that the
circuit breaker is closed.
Summary of Contents for Multilin 850
Page 10: ...VIII 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL ...
Page 135: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 41 ...
Page 151: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 57 ...
Page 153: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 59 ...
Page 439: ...CHAPTER 7 MONITORING FUNCTIONS 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 7 19 ...
Page 644: ...11 20 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 11 METERING ...