CHAPTER 7: MONITORING
TRIP AND CLOSE CIRCUIT MONITORING
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
7–5
Figure 7-6: Trip and Close Coil Circuit with Continuous Monitoring
Table 7-1: Value of Resistor “R”
DANGER:
Trip and Close Contacts must be considered unsafe to touch when the relay is
energized.
V
DC +
DC -
Output Relay 1 (TRIP)
52a
contact
Trip
Coil
FA_1
COM
FA_1
NO
FA_1
OPT/V
External
Jumper
R
Bypass
resistor
V
DC +
DC -
Output Relay 1 (TRIP)
52a
contact
Trip
Coil
FA_1
COM
FA_1
NO
FA_1
OPT/V
External
Jumper
R
Bypass
resistor
52a
contact
R
Bypass
resistor
V
DC +
DC -
Output Relay 2 (CLOSE)
52b
contact
Close
Coil
FA_2
COM
FA_2
NO
FA_2
OPT/V
External
Jumper
R
Bypass
resistor
V
DC +
DC -
Output Relay 2 (CLOSE)
52b
contact
Close
Coil
FA_2
COM
FA_2
NO
FA_2
OPT/V
External
Jumper
R
Bypass
resistor
52b
contact
R
Bypass
resistor
Power Supply (V DC)
Resistance (Ohms)
Power (Watts)
24
1000
2
48
10000
2
110
25000
5
125
25000
5
220
50000
5
Summary of Contents for Multilin 850
Page 10: ...VIII 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL ...
Page 135: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 41 ...
Page 151: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 57 ...
Page 153: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 59 ...
Page 439: ...CHAPTER 7 MONITORING FUNCTIONS 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 7 19 ...
Page 644: ...11 20 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 11 METERING ...