5–4
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
DEVICE
CHAPTER 5: DEVICE, SYSTEM, INPUT AND OUTPUT SETPOINTS
Example 2: More about the Function/Feature view control
The differences in the Input setpoints screens for Regular and Simplified mode are shown
below. Under Simplified mode, the
Virtual Inputs
and
Remote Inputs
are hidden for any
configuration change. However, the device will still accept and process virtual and remote
inputs based on what is configured during Regular mode. This way, Simplified
configuration mode does not change the behavior of the device.
Figure 5-3: Comparing the Inputs screens for Regular and Simplified mode
Path:
Setpoints > Device > Config Mode
CONFIG MODE
Range: Simplified, Regular
Default: Regular
This setting allows selection of the configuration mode while the device is accessed by
the “Administrator” role. In Regular configuration mode, all values in settings/functions
can be edited. In Simplified configuration mode, selected settings/functions are hidden
or the values are read-only to enhance user experience with minimum setpoint
changes.
Clock
Real-time Clock
Path
:
Setpoints > Device > Real Time Clock
The 850 is capable of receiving a time reference from several time sources in addition to its
own internal clock for the purpose of time-stamping events, transient recorders and other
occurrences within the relay. The accuracy of the time stamp is based on the time
reference that is used. The 850 supports an internal clock, SNTP, IRIG-B, and PTP IEEE 1588
as potential time references.
If two or more time sources are available, the time source with the higher priority shown in
Time Sources table is used where 1 is considered to be the highest priority. Please note
that the time source priority of PTP and IRIG-B can be swapped. If both PTP and IRIG-B are
available to the 850, by default the 850 clock syncs to PTP over IRIG-B. If PTP is not
available the 850 CPU syncs the internal clock to IRIG-B.
5HJXOD
r
Simplified
..\Setpoints\Inputs
Item Name
Contact Inputs
Virtual Inputs
Analog Inputs
Remote Inputs
Inputs
V Inputs
MA In
Rem In
..\Setpoints\Inputs
Item Name
Contact Inputs
Analog Inputs
Inputs
MA In
Summary of Contents for Multilin 850
Page 10: ...VIII 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL ...
Page 135: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 41 ...
Page 151: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 57 ...
Page 153: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 59 ...
Page 439: ...CHAPTER 7 MONITORING FUNCTIONS 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 7 19 ...
Page 644: ...11 20 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 11 METERING ...