6–146
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
FREQUENCY ELEMENTS
CHAPTER 6: PROTECTION SETPOINTS
CT INPUT
Range: dependant upon the order code
Default: CT Bank1-J1
This setting provides selection of the frequency input.
MINIMUM CURRENT
Range: 0.000 to 30.000 x CT in steps of 0.001 x CT
Default: 0.200 x CT
This setting defines the minimum current level required for operation of the element. The
supervising function responds to the positive-sequence current. Typical application
includes load shedding. Set the Pickup threshold to zero if no overcurrent supervision is
required. The setting of zero suspends the current supervision.
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
The element will be blocked when the selected operand is asserted.
OUTPUT RELAY X
For details see
Each relay can be selected to become either energized or de-energized when operated,
and to operate as latched, self-resetting or pulsed.
EVENTS
Range: Enabled, Disabled
Default: Enabled
The selection of the Enabled setting enables the events of the function.
TARGETS
Range: Disabled, Self-reset, Latched
Default: Self-reset
This setting is used to define the operation of an element target message. When set to
“Disabled,” no target message is issued upon operation of the element. When set to
“Self-Reset,” the target message and its LED indication follow the operate state of the
element, and self-reset once the operate element condition clears. When set to
“Latched,” the target message will remain visible after the element output returns to
logic 0 until a RESET command is received by the relay.
Summary of Contents for Multilin 850
Page 10: ...VIII 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL ...
Page 135: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 41 ...
Page 151: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 57 ...
Page 153: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 59 ...
Page 439: ...CHAPTER 7 MONITORING FUNCTIONS 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 7 19 ...
Page 644: ...11 20 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 11 METERING ...