CHAPTER 8: CONTROL
AUTORECLOSE
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
8–83
DELAY
Range: 0.000 to 6000.000 s in steps of 0.001 s
Default: 0.000 s
The setting establishes the extent of the additional Dead Time delay.
INCOMPLETE SEQUENCE TIME
Range: 0.000 to 6000.000 s in steps of 0.001 s
Default: 5.000 s
The timer defines the maximum time interval allowed for a single Reclose shot. It is
started whenever a Reclosure is initiated and is active when the scheme is in the
‘Reclose-in-Progress’ state. If all conditions allowing breaker closure are not satisfied
when this time expires, the scheme goes to Lockout.
FASTPATH:
This timer must be set to a delay less than the Reset timer.
RESET TIME
Range: 0.000 to 6000.000 s in steps of 0.001 s
Default: 60.000 s
The Reset timer is used to set the total time interval for a single fault event, from the first
trip until either Lockout or successful Reclosure. A Reset timer output resets the recloser
following a successful Reclosure sequence. The setting is based on the breaker ‘Reclaim
Time’ in a traditional scheme with fixed protection settings, which is the minimum time
required for the breaker to regain reclose cycle capability between successive Reclose
sequences. This time also must be set to a value greater than the maximum time to Trip
on each Reclose shot with a sufficient margin.
FASTPATH:
Set the RESET TIME timer to a delay longer than the INCOMPLETE SEQUENCE timer.
REDUCE MAXIMUM TO 1 (2 or 3)
Range: Off, Any FlexLogic operand
Default: Off
The setpoint selects the FlexLogic operand, digital input, virtual input or remote input
that changes the maximum number of shots from the initial setting to 1, 2 or 3.
SYNCHROCHECK SUPERV
Range: Bypass, Sync1 Close Perm, Sync 2 Close Perm
Default: Bypass
The setpoint selects Synchrocheck supervision. A closing signal from the Autoreclose
function can be supervised by the Synchrocheck function. The Synchrocheck function
has to be enabled and set accordingly. For applications where Synchrocheck and/or
Dead Source check is not needed, supervision can be bypassed. If the Synchrocheck
function is not selected in the order code, the setting is hidden and defaulted to Bypass.
FASTPATH:
If the supervision is not bypassed and Autoreclose is applied for an application where the
breaker is located on radial feeders, or line is powered by one source only, the DEAD
SOURCE PERM setpoint from the Synchrocheck menu shall not be disabled.
FASTPATH:
A Synchrocheck supervised Autoreclose CLOSE command is send directly to output #2. For
other outputs, logic has to be created for supervision, if needed.
ENABLED OUTPUT RELAY 3 (X)
Range: Do Not Operate, Operate
Default: Do Not Operate
Selects the relays required to operate while Autoreclosure is enabled. The selected
relays operate while the front panel Reclosure-enabled indicator is on.
Summary of Contents for Multilin 850
Page 10: ...VIII 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL ...
Page 135: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 41 ...
Page 151: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 57 ...
Page 153: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 59 ...
Page 439: ...CHAPTER 7 MONITORING FUNCTIONS 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 7 19 ...
Page 644: ...11 20 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 11 METERING ...