850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
OUTPUTS
CHAPTER 5: DEVICE, SYSTEM, INPUT AND OUTPUT SETPOINTS
Output Relay 2 (F4)
programmed as Close
Output Relay 2 (F4) is labeled CLOSE/AUX on the wiring diagram. As suggested by that
name, it can be used as a Close relay or an Auxiliary relay. This selection is made at
Setpoints > System > Breakers (Contactor) > Breakers 1 (Contactor 1) > Close Relay Select
. If
the selected value of the Close Relay Select setting is Off, Output Relay 2 functions as an
Auxiliary relay. If the selected value is Relay 2, Output Relay 2 functions as a Close relay.
The default value is Off. The description below applies to both Relay 2 “Close” functionality.
For the Relay 2 “auxiliary” functionality; see the
Figure 5-37:Auxiliary Relays generic logic
in the next section.
Path
:
Setpoints > Outputs > Output Relays > Aux Relay 2 (Close)
NOTE
NOTE:
The output relays selected under the Breaker menu for breaker closing are excluded from
the list of outputs for selection under the menus of all elements providing such output
relay selection.
NOTE
NOTE: For
If Aux Relay 2 is selected for Breaker Close or Contactor Close, the relay name from the
Output Relays menu changes to “Close”. If Aux Relay 2 is not selected, the name reverts to
“Aux Relay 2”.
Summary of Contents for Multilin 850
Page 10: ...VIII 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL ...
Page 135: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 41 ...
Page 151: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 57 ...
Page 153: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 59 ...
Page 439: ...CHAPTER 7 MONITORING FUNCTIONS 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 7 19 ...
Page 644: ...11 20 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 11 METERING ...