7–2
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
TRIP AND CLOSE CIRCUIT MONITORING
CHAPTER 7: MONITORING
Trip and Close Circuit Monitoring
The 850 relay provides Trip and Close Circuit Monitoring elements.
The first and second Form A relay outputs on slot “F” include a circuit to monitor the DC
voltage across the output contact when it is open. To do that, an external jumper is wired
between the terminals “FA_1 COM” and “FA_1 OPT/V” for the Trip coil monitoring, or/and
“FA_2 COM” and “FA_2 OPT/V” for the Close coil monitoring.
The monitor contains a level detector whose output is set to logic 1 (ON) when the voltage
is above 20 volts. The voltage monitor is used to check the health of the overall trip and
closing circuit.
The two figures below show the two different connections of the breaker trip and close
coils to the relay’s trip and close output relays for either no voltage monitoring and for
voltage monitoring of the circuits.
Figure 7-2: Trip Coil Circuit without Monitoring
V
DC +
DC -
Output Relay 1 (TRIP)
52a
contact
Trip
Coil
FA_1
COM
FA_1
NO
FA_1
OPT/V
Summary of Contents for Multilin 850
Page 10: ...VIII 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL ...
Page 135: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 41 ...
Page 151: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 57 ...
Page 153: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 59 ...
Page 439: ...CHAPTER 7 MONITORING FUNCTIONS 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 7 19 ...
Page 644: ...11 20 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 11 METERING ...