850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
AUTORECLOSE
CHAPTER 8: CONTROL
FUNCTION
Range: Disabled, Enabled
Default: Disabled
SIGNAL INPUT
Range: dependant upon the order code
Default: CT Bank 1-J1
This setting provides the selection for three-phase current input used for deriving the
phase and neutral currents.
PHASE CURRENT PICKUP
Range: 0.050 to 30.000 x CT in steps of 0.001 x CT
Default: 1.000 x CT
The setpoint specifies phase fault current level, which when exceeded, signifies a
downstream fault.
FASTPATH:
These currents may be quite low for an end fault on a long feeder with a weak source.
NEUTRAL CURRENT PICKUP
Range: 0.050 to 30.000 x CT in steps of 0.001 x CT
Default: 0.300 x CT
The setpoint specifies neutral fault current level, which when exceeded, signifies a
downstream fault.
PICKUP TIME
Range: 0.000 to 6000.000 s in steps of 0.001 s
Default: 0.020 s
If the (phase or neutral) fault current exists for more than the Coordination Pickup Time
scheme, an increase in fault current magnitude is declared.
DROPOUT TIME
Range: 0.000 to 6000.000 s in steps of 0.001 s
Default: 0.020 s
If the (phase or neutral) fault current drops, the downstream Reclose opening is declared
for the duration of Coordination Dropout Time.
EVENTS
Range: Disabled, Enabled
Default: Enabled
Summary of Contents for Multilin 850
Page 10: ...VIII 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL ...
Page 135: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 41 ...
Page 151: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 57 ...
Page 153: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 59 ...
Page 439: ...CHAPTER 7 MONITORING FUNCTIONS 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 7 19 ...
Page 644: ...11 20 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 11 METERING ...