CHAPTER 10: STATUS
CLOCK STATUS
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
10–15
TRIP
Range: YES, NO
Default: NO
ACTIVE GROUP
Range: SP Group 1-6 Active
Default: SP Group 1 Active
Clock Status
Path
:
Status > Clock
SYSTEM CLOCK
Range: MMM DD YY HH:MM:SS
The current date and time of the system clock is displayed here.
RTC SYNC SOURCE
Range: None, Port 4 PTP Clock, Port 5 PTP Clock, IRIG-B, SNTP Server 1, SNTP Server 2
The
RTC Sync Source
actual value is the time synchronizing source the relay is using at
present.
PTP Status
The present values of the PTP protocol are displayed here.
Path
:
Status > PTP
Grandmaster ID
is the grandmaster Identity code being received from the present PTP
grandmaster, if any. When the relay is not using any PTP grandmaster, this actual value is
zero. The grandmaster Identity code is specified by PTP to be globally unique, so one can
always know which clock is grandmaster in a system with multiple grandmaster-capable
clocks.
RTC Accuracy
is the estimated maximum time difference at present in the Real Time Clock
(RTC), considering the quality information imbedded in the received time signal, how long
the relay has had to lock to the time source, and in the case of time signal interruptions,
the length of the interruption. The value 999,999,999 indicates that the magnitude of the
estimated difference is one second or more, or that the difference cannot be estimated.
Port 4 (5) PTP State
is the present state of the port’s PTP clock. The PTP clock state is:
•
DISABLED
If the port’s function setting is Disabled
•
NO SIGNAL
If enabled but no signal from an active master has been found and selected
•
CALIBRATING
If an active master has been selected but lock is not at present established
•
SYNCH’D (NO PDELAY)
If the port is synchronized, but the peer delay mechanism is non-operational
•
SYNCHRONIZED
If the port is synchronized
Summary of Contents for Multilin 850
Page 10: ...VIII 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL ...
Page 135: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 41 ...
Page 151: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 57 ...
Page 153: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 59 ...
Page 439: ...CHAPTER 7 MONITORING FUNCTIONS 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 7 19 ...
Page 644: ...11 20 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 11 METERING ...