9–8
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
FLEXLOGIC
CHAPTER 9: FLEXLOGIC AND OTHER SETPOINTS
Local Control Mode
SBO Enabled
Local Mode ON
Local Mode OFF
BKR[X] Local Open
BKR[X] Local Close
BKR[X] Loc Blk Open
BKR[X] Loc Blk Close
BKR[X] Loc Blk Open By
BKR[X] Loc Blk Cls By
BKR[X] Tag On
BKR[X] Tag Off
BKR[X] Selected
SW[X] Local Open
SW[X] Local Close
SW[X] Loc Blk Open
SW[X] Loc Blk Close
SW[X] Loc Blk Open By
SW[X] Loc Blk Cls By
SW[X] Tag On
SW[X] Tag Off
SW[X] Selected
Select Before Operate control mode is enabled
Local mode is ON (shows LM in display banner)
Local mode is OFF
Local Open command has been initiated to BKR[X]
Local Close command has been initiated to BKR[X]
Open command to BKR[X] is blocked
Close command to BKR[X] is blocked
Open command to BKR[X] is permitted, Block Open signal is bypassed
command to BKR[X] is permitted, Block Close signal is bypassed
The selected breaker is tagged
The selected breaker is untagged
Breaker BKR[X] has been selected in SLD
Local Open command has been initiated to SW[X]
Local Close command has been initiated to SW[X]
Open command to the switch is blocked
Close command to the switch is blocked
Open switch command is permitted, Block Open signal is bypassed
Close switch command is permitted, Block Close signal is bypassed
The selected breaker/switch is tagged
The selected breaker/switch is untagged
Disconnect Switch 1(8) has been selected in SLD
[X] - the element number.
Loss of Communications
Loss Of Comms PKP
Loss Of Comms OP
Loss Of Comms has picked up
Loss Of Comms has operated
Manual Close Blocking
Manual Cls Blk OP
Manual Close Blocking element has operated
Neutral Admittance
Ntrl Admit PKP
Ntrl Admit OP
Neutral admittance has picked up
Neutral admittance has operated
Neutral TOC
Ntrl TOC 1 PKP
Ntrl TOC 1 OP
Ntrl TOC 2
Neutral time overcurrent 1 has picked up
Neutral time overcurrent 1 has operated
The same set of operands as per Neutral TOC 1
Neutral IOC
Ntrl IOC 1 PKP
Ntrl IOC 1 OP
Ntrl IOC 2
Neutral IOC 1 has picked up
Neutral IOC 1 has operated
The same set of operands as per Neutral IOC 1
Neutral Directional OC
Ntrl Dir OC FWD
Ntrl Dir OC REV
Neutral directional overcurrent forward has operated
Neutral directional overcurrent reverse has operated
Neutral OV
Ntrl OV [X] PKP
Ntrl OV [X] OP
Neutral overvoltage element 1 has picked up
Neutral overvoltage element 1 has operated
Negative sequence OV
NegSeq OV 1 PKP
NegSeq OV 1 OP
Negative-sequence overvoltage element 1 has picked up
Negative-sequence overvoltage element 1 has operated
Negative Sequence TOC
NegSeq TOC 1 PKP
NegSeq TOC 1 OP
Negative Sequence TOC 1 has picked up
Negative Sequence TOC 1 has operated
Negative Sequence IOC
NegSeq IOC 1 PKP
NegSeq IOC 1 OP
Negative Sequence IOC has picked up
Negative Sequence IOC 1 has operated
Negative Sequence
Directional OC
NegSeq DirOC [X] FWD
NegSeq DirOC [X] REV
Negative Sequence directional overcurrent forward has operated
Negative Sequence directional overcurrent reverse has operated
[X] - the element number
Non-Volatile Latch 1 to 16 NV Latch 1 ON
NV Latch 1 OFF
Any PKP
Any OP
Any Trip
Any Alarm
NV Latch 2 to 16
The output of non-volatile latch 1 is On
The output of non-volatile latch 1 is Off
Any enabled protection or control element pickup
Any enabled protection or control element operated
Any operated element with Function selected as “Trip”
Any operated element with Function selected as “Alarm”
The same set of operands as per Non-Volatile Latch 1
Output Relays
Trip ON
Close ON
Aux Relay [X] ON
BKR [X] Manual Open
BKR [X] Manual Close
Trip command to Relay 1 (TRIP) has been issued
Close command to Relay 2 (CLOSE) has been issued
Command to Aux Relay [X] has been issued
Either Local (using PBs) Open or Remote Open command has been issued
to the output relay selected under BKR[X] Trip Relay Select setpoint
Either Local (using PBs) Close or Remote Close command has been issued
to the output relay selected under BKR[X] Close Relay Select setpoint
Over-Frequency
Overfreq 1 PKP
Overfreq 1 OP
Overfreq 2
Overfrequency 1 has picked up
Overfrequency 1 has operated
The same set of operands as per Overfreq 1
ELEMENT
OPERANDS
EVENT DESCRIPTION
Summary of Contents for Multilin 850
Page 10: ...VIII 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL ...
Page 135: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 41 ...
Page 151: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 57 ...
Page 153: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 59 ...
Page 439: ...CHAPTER 7 MONITORING FUNCTIONS 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 7 19 ...
Page 644: ...11 20 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 11 METERING ...