CHAPTER 6: PROTECTION SETPOINTS
ADMITTANCE
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
6–121
Y0 REACH
Range: 0.00 to 500.00 mS in steps of 0.01 mS
Default: 1.00 mS
This setting defines the reach of neutral admittance based protection criterion. Neutral
Admittance Ground Fault protection will operate after the set Pickup Delay time when
the neutral admittance quantity, Y0, exceeds this reach level. Regardless of the Direction
setting, this element always operates in the non-directional mode. Operating
characteristic depends only on the pick-up threshold defined by this setting.
G0 FWD REACH
Range: -500.00 to 500.00 mS in steps of 0.01 mS
Default: 1.00 mS
This setting defines the pickup level of protection criterion based on the neutral
conductance. Neutral Admittance Ground Fault protection will operate after the set
Pickup Delay time when the neutral conductance quantity, G0, exceeds the reach level
defined by this setting. This setting is not applicable when the Direction setting is set to
Reverse.
jB
G
Y0
Operate
Block
Summary of Contents for Multilin 850
Page 10: ...VIII 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL ...
Page 135: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 41 ...
Page 151: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 57 ...
Page 153: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 59 ...
Page 439: ...CHAPTER 7 MONITORING FUNCTIONS 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 7 19 ...
Page 644: ...11 20 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 11 METERING ...