7–32
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
FUNCTIONS
CHAPTER 7: MONITORING
Pulsed Outputs
The 850 relay provides a Pulse Output element for four energy measurements. The
element can operate auxiliary relays after an adjustable energy increment for the
quantities of positive and negative MWatthours and positive and negative MVARhours.
Pulses occur at the end of each programmed energy increment. Upon power-up of the
relay, the Pulse Output function, if enabled, continues from where it was at the time of loss
of control power. For example, if control power is removed when the positive Watthours
stored at last pulse was 24.000 MWh, when control power is re-applied a pulse occurs at
34.000 MWh if the energy increment is set at 10.000 MWh.
FASTPATH:
1.
The Auxiliary Output relay(s) used for this element must be set to “Self-Resetting”
under Aux Output relays. The pulses consist of a one second on-time and a one
second off-time. This feature is programmed such that no more than one pulse per
two seconds is required.
2.
The 850 is not a revenue class meter and cannot be used for billing purposes.
Energy quantities are displayed in MWh and MVarh, with resolutions of 1 kWh and 1 kVarh
respectively.
Path
:
Setpoints > Monitoring > Functions > Pulsed Outputs
FUNCTION
Range: Disabled, Enabled
Default: Disabled
SIGNAL INPUT
Range: Power 1, Power 2, Power 3, Power 4, Dependant on order code
Default: Power 1
This setting provides the power element selection for the CT and VT bank identification.
POS WHS PULSE INCREMENT
Range: 0.000 to 1000.000 MWh in steps of 0.001 MWh
Default: 10.000 MWh
The setpoint specifies the positive Watthours threshold pulse increment after which the
output pulse and output operand are set.
POS WHS PULSE RELAY X
For details see
NEG WHS PULSE INCREMENT
Range: 0.000 to 1000.000 MWh in steps of 0.001 MWh
Default: 10.000 MWh
The setpoint specifies the negative Watthours threshold pulse increment after which the
output pulse and output operand are set.
NEG WHS PULSE RELAY X
For details see
POS VARHS PULSE INCREMENT
Range: 0.000 to 1000.000 MVARh in steps of 0.001 MVARh
Default: 10.000 MVARh
The setpoint specifies the positive VARhours threshold pulse increment after which the
output pulse and output operand are set.
POS VARHS PULSE RELAY X
For details see
Summary of Contents for Multilin 850
Page 10: ...VIII 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL ...
Page 135: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 41 ...
Page 151: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 57 ...
Page 153: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 59 ...
Page 439: ...CHAPTER 7 MONITORING FUNCTIONS 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 7 19 ...
Page 644: ...11 20 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 11 METERING ...