8–64
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
BUS TRANSFER
CHAPTER 8: CONTROL
FASTPATH:
The #2 CLOSE OUTPUT relay is blocked if Transfer is enabled, but blocked while the breaker
is connected (racked-in). If breaker closing is required during maintenance, Transfer must
be disabled.
EVENTS
Range: Disabled, Enabled
Default: Enabled
TARGETS
Range: Disabled, Self-reset, Latched
Default: Self-reset
850 RELAY – INCOMER 2
When INCOMER 2 function is selected the following display is available:
INC 2 CB CONNECTED
Range: Off, Any FlexLogic operand
Default: Off
The setpoint selects the FlexLogic operand, digital input, virtual input or remote input
used to inhibit transfer if Incomer breaker 2 cannot be used to pass current from the
source to the load (for example when the breaker is in rack-out or test position). This
setpoint also provides the condition for “Selected to Trip” breaker logic, FlexLogic
operand INC2 CB CON & CLSD required for Incomer 2 Circuit Breaker transfer logic, Bus
Tie Circuit Breaker transfer logic, and for blocking #2 close relay.
FASTPATH:
For non-draw-out breakers without associated disconnect switches, this setpoint must be
set as ON.
Summary of Contents for Multilin 850
Page 10: ...VIII 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL ...
Page 135: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 41 ...
Page 151: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 57 ...
Page 153: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 59 ...
Page 439: ...CHAPTER 7 MONITORING FUNCTIONS 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 7 19 ...
Page 644: ...11 20 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 11 METERING ...