1–36
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
SPECIFICATIONS
CHAPTER 1: INTRODUCTION
DOUBLE POLE OUTPUT RELAYS, I/O CARD D
Maximum Working Voltage: ..........................300 VDC / 300 VAC
Make and short-time carry current: ..........30A/0.2s per IEEE C37.90
Maximum Continuous Current per
contact:..............................................................5A
Total maximum current for contacts
connected to common potential:..........10A
Breaking Capacity (DC inductive) with
respect to source voltage, @L/R = 40
ms (10000 Operation, per IEC 60255-1
2009-08): ...........................................................24 V - 1 A
48 V - 0.5 A
125 V - 0.3 A
250 V - 0.2 A
Breaking Capacity (DC resistive) with
respect to source voltage:.........................24 V - 8 A
48 V - 2 A
125 V - 0.3 A
250 V - 0.2 A
Breaking Capacity (AC inductive) with
respect to source voltage, @PF= 0.35
or less:.................................................................B300, Pilot duty
360 VA
Breaking Capacity (AC resistive) with
respect to source voltage:.........................277 V - 5 A
Operating Time (coil energization to
contact closure, resistive load):...............<8ms
Contact Material: ................................................Silver alloy
Mechanical Endurance (no load):................> 10,000
Maximum Frequency of operation: ...........360/h
Protection Device across contact:..............EMI Suppression Cap, 1nF
Summary of Contents for Multilin 850
Page 10: ...VIII 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL ...
Page 135: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 41 ...
Page 151: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 57 ...
Page 153: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 59 ...
Page 439: ...CHAPTER 7 MONITORING FUNCTIONS 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 7 19 ...
Page 644: ...11 20 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 11 METERING ...