6–120
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
ADMITTANCE
CHAPTER 6: PROTECTION SETPOINTS
ANGLE CORRECTION
Range: 0.0 to 359.0° in steps of 0.1°
Default: 0.0°
This setting specifies the correction angle between current and voltage.
In addition, this setting can be used to correct the relative polarity of the ground current
with respect to voltage. If the polarity of the current is reversed or not relative to voltage,
this setting can be used to change the polarity. When “180 deg” is selected, the
measured admittance Y0 is multiplied with -1 which corresponds to a 180 degree shift in
current direction.
Secondly, this angle can also be used to eliminate the angular errors of the voltage
transformer and/or current transformers (CT); measured phase angle deviations caused
by measuring inaccuracy of voltage transformers, can be eliminated by properly setting
this value.
jB
G
)
(
0
0
0
0
0
V
I
V
I
Y
)
(
180
0
0
0
0
0
V
I
V
I
Y
jB
G
Y0
Y0"
Y0'
Y0-
ƀ
c
Y0+
ƀ
c
Summary of Contents for Multilin 850
Page 10: ...VIII 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL ...
Page 135: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 41 ...
Page 151: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 57 ...
Page 153: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 59 ...
Page 439: ...CHAPTER 7 MONITORING FUNCTIONS 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 7 19 ...
Page 644: ...11 20 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 11 METERING ...